Search results for "narrow band power line communication"
showing 10 items of 10 documents
A new low cost power line communication solution for smart grid monitoring and management
2018
Modern smart grids require the improvement of measurement and communication infrastructures of distribution networks, at both medium voltage (MV) and low voltage (LV) levels. Distributed sensing and measurement systems are needed to provide all necessary data for grid monitoring, control and management, as well as for the implementation of a number of smart functionalities, such as remote control of distributed generators (DGs), real time analysis of power flows, automatic meter reading (AMR), demand side management (DSM), grid automation and so on [1]-[6]. Acquired network data include typical electrical network quantities and status variables (such as powers, voltages, currents, switches …
A New Coupling Solution for G3-PLC Employment in MV Smart Grids
2019
This paper proposes a new coupling solution for transmitting narrowband multicarrier power line communication (PLC) signals over medium voltage (MV) power lines. The proposed system is based on an innovative PLC coupling principle, patented by the authors, which exploits the capacitive divider embedded in voltage detecting systems (VDS) already installed inside the MV switchboard. Thus, no dedicated couplers have to be installed and no switchboard modifications or energy interruptions are needed. This allows a significant cost reduction of MV PLC implementation. A first prototype of the proposed coupling system was presented in previous papers: it had a 15 kHz bandwidth useful to couple sin…
Experimental investigation on PLC signal crossing of power transformers
2014
In this work the use of PLC in MV-LV networks is investigated, by means of experimental tests in the case of a two-ways MV/LV communication between two secondary substations. The two substations are connected by a MV overhead power line. Moreover each substation has a by-pass connection at MV bus-bars and a MV/LV power transformer. A ST7580 transceiver is used to inject the communication signal. The transceiver is embedded in a new interface device developed by the authors. In the paper the communication issues are introduced and some experimental tests are presented and discussed. Such tests have been carried out in the presence of voltage net, i.e. 24 kV, with the aim to verify the possib…
A New Low Cost Coupling System for Power Line Communication on Medium Voltage Smart Grids
2018
This paper proposes and verifies the performance of an innovative and low cost coupling system for power line communication (PLC) on medium voltage (MV) smart grids. The coupling system makes use of the capacitive divider of the voltage detecting systems (VDSs) to inject and receive the PLC signal. VDS are usually already installed in the MV switchboards of the major electrical manufacturer all over the world according to IEC 61243-5. VDS are used to detect the presence of the mains voltage to guarantee personnel safety. An interface circuit has been developed to be connected between the PLC transceiver and the VDS socket. In this way, the PLC signal can be coupled to the MV network without…
Medium Voltage Smart Grid: Experimental Analysis of Secondary Substation Narrow Band Power Line Communication
2013
This paper is focused on the possibility of employing narrow band power line communication (PLC) in medium voltage (MV) distribution networks. The topic is investigated by means of both simulations and experimental tests, which were carried out in the distribution network of Ustica Island. In detail, a two-way MV communication was tested between two secondary substations connected by an MV cable power line. Each substation has a by-pass connection at MV bus-bars and an MV/LV oil filled power transformer. In this paper, the MV and the PLC systems under test are described and the experimental tests are presented, which were carried out to evaluate the parameters of the simulation model. The a…
Narrowband power line communications for medium voltage smart grids
2014
The aim of the paper is to show how narrowband power line communications (NB-PLCs) can be a valid solution for medium voltage grids. Advantages and drawbacks of this solution are analyzed, starting from some experimental communication results, which were carried out on the medium power system networks of the islands of Ustica and Favignana, in the presence of the net voltage. Furthermore, some communication architectures and hardware prototypes based on NB-PLCs are proposed for different smart grids applications.
Development of a Coupling System for Medium Voltage Power Line Communication in the CENELEC A Frequency Band
2016
In this paper the performances of a new power line communication (PLC) coupling system for medium voltage (MV) smart grids are investigated in the CENELEC A frequency band (i.e. 3 - 95 kHz). The new coupling solution is based on the use of the capacitive divider of the voltage detecting system (VDS) as PLC coupler to the MV network. According to IEC 61243-5, VDS are worldwide used to reveal the presence of the mains voltage to ensure the safety of the operators. A proper interface circuit has been invented and patented to couple the PLC signal through the VDS. In this way no dedicated MV PLC coupler is required, thus avoiding the related costs of the coupler, of its installation, and those …
Design and Characterization of a New MV PLC Coupler for Smart Electric Energy Systems
2018
This paper deals with the design, modeling and characterization of a new coupling system for medium voltage (MV) narrow band power line communications (NB-PLC). It exploits the capacitive divider of voltage detecting systems (VDSs) normally used to reveal the mains voltage presence, thus avoiding the use of dedicated MV couplers. The proposed coupling system was patented by the authors. In this paper, the modeling of the VDS capacitive divider is presented, using a proper characterization method. Moreover, the interface card design is described, based on simulation of the whole PLC transmission channel. Laboratory tests are also presented and discussed. More in detail, a frequency response …
Experimental Evaluation on Narrow Band Power Line Communication in Medium and Low Voltage Smart Grids
2013
The aim of this work is to perform a feasibility study on the power line communication for the development of a new generation of interface devices (IDs) for smart grid and energy storage applications. More in detail, this paper deals with one of the most important issues on this topic, which is the communication system. Among the existing communication technologies, the study is focused on power line communications (PLCs). After an analysis of the state of the art in the field, the main aspects are analyzed, concerning the open issues on the use of PLCs, especially for medium voltage (MV) and low voltage (LV) systems. In this work the use of PLC in MV-LV networks is investigated, by means …
An Innovative Power Line Communication solution For Medium Voltage Smart Grids Applications
2018
This paper summarizes the authors research activity concerning the design, modeling and experimental characterization of a new coupling system for medium voltage (MV) narrow band power line communications (NB-PLC). The proposed solution has been patented by authors and it exploits the capacitive divider of voltage detecting systems (VDSs) normally used to reveal the mains voltage presence, thus avoiding the use of dedicated MV couplers. In the following, the modeling of the VDS capacitive divider is presented and the interface card design is described, based on simulation of the whole PLC transmission channel. Laboratory tests are also presented. Finally, the results are shown of an on-fiel…